Home-Spec Inspections LLC

                         ASHI Certified Home Inspections

                                     We Inspect Colorado!

                                      

                      Aurora Arvada Broomfield Boulder Denver Golden

                               Lakewood Littleton Parker Westminster

 

100_4810.jpg

 

                                 ASHI Certified Inspection for

Client:  Tony Garrett

Inspection Address:  902 Sleepy Hollow Dr  Golden, CO 80401

Date:  Thursday,  March 19, 2007

At least 20 color photos are included with every inspection report!

 

INSPECTOR’S OVERALL RATING:

This 1960’s home appears to have been adequately constructed.  The basic components:  lot, roof, foundation, structure, boiler, electrical and plumbing appear to be old but still in acceptable condition. The water heater and furnace appear to be near the end of their life.  This home is 40 plus years old and should be expected to display the wear and tear of an older house.  Most older houses require an above average amount of work to keep them well maintained.  Recent on-going maintenance on this house has been above average; however, several deficiencies were observed.

SIGNIFICANT FAULTS:

Lot located on major highway – significant road noise

Debris/trash storied against house is a fire hazard

Asphalt shingle roof has moderate wind damage – immediate repair

Minor sag in garage roof overhang, probably caused by snow load – garage roof structure looks OK

Weather stripping on bottom of garage door needs to be replaced

North fence gate needs repair

Few broken/cracked bricks around lower windows

Front bay window exterior siding is in contact with the soil – move soil away from siding

Front door is hollow core, not suitable for exterior use – replace in 1 year plan

Wood trim around windows shows some dry rot and needs immediate painting/repair
Garage door springs are weak making the door difficult to open – adjust springs
Furnace and water heater show signs significant of deterioration – replace in one year

North kitchen door knob plunger and strike need adjusting

Several windows have single pane glass and are difficult to open

Several ceramic tile window sills cracked

All plumbing pipes appear to be galvanized steel – will have significant effect on resale value

Hard water stain on bathroom fixtures – recommend installing a water softener

Main floor tub drain plug needs adjusting

Pocket door to bathroom is not plumb and does not latch – needs to be re-installed

Furnace room floor drain needs repair

Fire brick in both fireplace has some cracking

No fan in laundry room

 

SAFETY ITEMS:
Carbon monoxide concentration is greater than 35 PPM(parts per million) in furnace room. 

     Do not occupy house until furnace burner is adjusted by a gas furnace repair service.

An Infrared scan of main electrical panel identified a hot main terminal (109F) at the top left of

     the panel.  Have electrician tighten all terminals in the panel.

The bottom of the stairway leading to the basement needs to be enclosed with fire resistant sheetrock to protect the stairs for exit during a fire.

 

COMPONENTS NEAR THE END OF THEIR SERVICE LIFE
Furnace has less than 3 years of service life left
Water heater has less than 1 years of service life left
Roof has less than 8 years of service life left

 

SUGGESTED ITEMS TO ASK CURRENT OWNER TO FIX
Furnace repair to reduce carbon monoxide level

  Remove debris from yard
Replace damaged roof shingles
Replace front door with a solid core, weather proof door
Adjust garage door springs

  Replace weather stripping on bottom of garage door

  Adjust main bath tub drain

  Repair bathroom pocket door

 

ROOF
The 3-tab asphalt shingle roof appears to be in adequate condition except for moderate wind damage and nail penetration on the southeast side that appears to be causing water to leak into the attic structure.. You can expect about 8 more years before replacing the roof. The flashing, drainage and gutters appear to be functional with no visual defects. Furnace vent and waste vent penetrations appear to be adequate. Attic vents penetrating the roof appear properly installed and in satisfactory condition. Rain gutters surround the entire house are in satisfactory condition.

STRUCTURAL SYSTEM
The 8" thick concrete foundation walls show no cracks or signs of movement and appear to be in good condition. Accessible wood 2x8" structural framing in the attic areas show no sign of degradation and appears solid when probed. Roof trusses appear to be in good condition, with no sign of water damage or sagging
.  Standing in the driveway, you can see a slight sag in the garage roof. No structural damage was obvious in the garage attic. Floor joist and studs visible in the basement storage appear sound. Concrete floor in basement appears to be level and without visual cracks.

EXTERIOR
Exterior walls are in below average condition and will need painting soon. Soffits and window trim show signs of significant dry rot.  Several windows are the single pane type. Front porch, walkways and driveway seem to be in good condition.  Lawn and bushes appear healthy.  Back patio is constructed with 2x4 wood decking and feels solid when walked on. The west side of the patio in contact with the earth. I suggest that some soil be moved back from the patio. Garage door safety switch works OK. Storm drainage appears OK.

INTERIOR
Ceiling and walls are finished with sheetrock and recently painted. The older sheetrock shows signs of slight taping separation at a few joints. Floors appear sound and level. Interior doors are
functional. The stairs and railing appear OK. Underside of the stairs needs fire proofing. Cabinets and counters are well mounted and secure. Closet space is adequate. The basement bedrooms do not have adequate ways to exit during a fire.

ELECTRICAL SYSTEM
The electrical service is located in the garage. A 125 amp service is slightly small for this size house. No future capacity is available. All visible wiring is copper.
An infrared scan of the panel revealed hot spot in the phase B (leftside) main terminal. I suggest having an electrician tighten the phase B lug. The grounding system is grounded to the hot and cold water pipes and to a ground rod. There are no GFI receptacles in the kitchen, bathrooms or garage. Older houses were wired with two wires instead of the currently used 3-wire system; so most of the receptacles in this house are the two-prong type. Many appliances will not plug into two prong receptacles without an adapter. The three-way light switches in the stairway need to be wired correctly. Generally older houses have fewer receptacles than modern houses. Smoke detector in the hallway functioned normally when tested. I suggest adding smoke detectors in the basement.

PLUMBING SYSTEM
The main water pipe into the house is 3/4" galvanized steel and the feeder lines within the house are ½" and ¾" galvanized steel. Hot water is provided by a 40 gal, gas, Bradford White water heater. Lavatories and toilets function normally. Accessible waste piping is cast-iron pipe and appears to function adequately. Sewage is handled by the city and was not inspected. In general the plumbing system is quiet with no unusually loud water or sewer noises. The clothes dryer is electric only.

HEATING AND COOLING SYSTEM
Heating is provided by an older Foster Johnston forced air, gas furnace located in the basement
bathroom area. A carbon monoxide test found a 35 ppm CO level in the furnace room. I suggest having a furnace repairman adjust the gas/air ratio for the burner. No combustible gas was detected. The system is moderately noisy. Cooling is provided by an evaporative cooler on the roof. The ductwork appear to be adequate. A programmable, setback thermostat located in the dining room provides controls. The duct appears to cover each room and is in adequate condition.

VENTING AND INSULATION
The attic is insulated with cellulose. The cellulose has settled quite a bit over the years. I recommend blowing in fiberglass insulation on top of the cellulose. Exterior wall insulation was not visible. There is no insulation in the garage ceiling. The attic vents appear to be properly sized and functional. Bathroom fans worked OK. The exhaust fan above the kitchen range appears weak. A vapor barrier was not apparent in the ceiling or walls.

FIREPLACES AND STOVES
One wood burning fireplace was observed. The fire box and fire brick have some cracking.
The damper chain is missing or broken leaving the damper in a constant open position. Attaching a new chains appears to be a simple undertaking. Clearances around the fireplace appear to be adequate.

Home